The solution for
> Professional workstations
> Industrial automation
> Security systems
> Telecom systems
> Banking ATM systems
The best electrical protection
• True online double conversion technology
(VFI) assures high availability and total load
protection.
• Constant output voltage and frequency
regulation makes ITYS E compatible
with different applications, operating
environments and GenSets
• Automatic bypass supplies the loads in the
event of overloads or faults.
Robust and versatile
• Compact tower UPS system saves space in
the operating environment
• No special configuration on first startup.
• Easy connections via sockets or terminals.
• Wide input voltage tolerance limits the
switchovers to battery mode prolonging the
battery life.
• Manual bypass for periodic or emergency
maintenance
Standard communication features
• LOCAL VIEW: ideal UPS monitoring and
shutdown point-to-point solution for
Windows®, Linux and Mac OS X® operating
systems.
• HID: UPS management based on Windows®
and Mac OS X® embedded service - USB
interface.
Communication options
• Dry-contact card for UPS remote
diagnostic (ITY-E-OP-REL).
Related
Specification
View connection

1.USB serial port.
2. RS232 serial port.
3. Shut down the UPS remotely.
4. Dry contact interface.
5. Slot for optional communication board.
6. Manual shortcut.
7. Input protection (heat cut-out).
8. Battery detection.
9. Wheels
10. Board input and output terminals.
11. Connection for a modular battery extension.
12. Output socket (IEC 320 – C13).
13. Input socket (IEC 320).
14. Output jack (IEC 320 – C19).
(1) Input and output terminal (3 kVA – model without internal batteries)
|
ITYS E – UPS |
| Sn |
1000 VA |
2000 VA |
3000 VA |
6000 VA |
10000 VA |
| Pn |
800 W |
1600 W |
2400 W |
4800 W |
8000 W |
| Input |
| Voltage |
230 V (1ph) 160÷300 V up to 110 V @ 60% load |
| Rated frequency |
50/60 Hz |
| Power factor |
0.99 |
| Output |
| Rated voltage |
208 / 220 / 230 / 240 V |
| Voltage tolerance |
± 1% |
| Rated frequency |
50/60 Hz (46÷54 Hz / 56÷64 Hz) (in battery mode 50/60 ± 0.1 Hz) |
| Overload |
Up to 130% for 1 minute |
| Crest factor |
3:1 |
| Connections |
| IEC standard |
3 x IEC 320 |
4 x IEC 320 |
4 x IEC 320 + terminals |
terminals |
| Universal standard |
2 sockets |
2 sockets |
2 sockets + terminals |
terminals |
| Indian standard |
3 sockets |
4 sockets |
4 sockets + terminals |
terminals |
| Batteries |
| Type |
sealed lead-acid maintenance free – expected life 3/5 years |
Back-up time @75% of rated VA load pf 0.7
(Models with internal batteries) |
8 min |
9 min |
| Voltage (Models without batteries) |
36 VDC |
96 VDC |
192 VDC |
240 VDC |
| Battery charger (Models without batteries) |
Setting up to 6 A |
| Communication |
| Interfaces |
RS232 – USB |
| Local communication software |
Local View |
| Efficiency |
| Online mode |
up to 90 % |
| Environment |
| Ambient service temperature |
0 °C to +40 °C (15 °C to 25 °C for maximum battery lifetime) |
| Relative humidity |
0 to 95% without condensation |
| Maximum altitude |
1000 m without derating |
| Noise level at 1 m |
< 55 dBA |
< 59 dBA |
| UPS CABINET (Models with internal batteries) |
| Dimensions W x D x H |
145 x 285 x 220 mm |
145 x 400 x 220 mm |
190 x 425 x 320 mm |
190 x 370 x 640 mm |
190 x 450 x 640 mm |
| Weight |
10 kg |
17 kg |
28 kg |
60 kg |
75 kg |
| Degree of protection |
IP20 |
| UPS CABINET (Models without batteries) |
| Dimensions W x D x H |
145 x 285 x 220 mm |
145 x 400 x 220 mm |
145 x 400 x 220 mm |
190 x 370 x 320 mm |
190 x 450 x 320 mm |
| Weight |
5 kg |
7 kg |
8 kg |
12 kg |
16 kg |
| Degree of protection |
IP20 |
| Standards |
| Safety(1) |
EN 62040-1 |
| EMC(1) |
EN 62040-2 |
| Product declaration(1) |
CE |
| BIS certification |
R-41030651 |
R-41120790 |
|
(1) Models with IEC output sockets.
Related